Property Address:
1287 silver perch
las vegas nv 89123
![]() |
Joseph Chan
123 company address
Las Vegas NV 89102
(702) 309-8668
| Date: 9/15/2011 | Time: 05:38 PM | Report ID: 11091501 |
| Property: 1287 silver perch las vegas nv 89123 |
Customer: Mr. first house customer |
Real Estate Professional: |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
|
In
Attendance:
Vacant (inspector only) |
Type
of building:
Single Family (2 story) |
Approximate
age of building:
Over 10 Years |
|
Temperature:
over 90 (F) |
|
Roof
Covering:
Tile |
Viewed
roof covering from:
Ground |
Chimney
(exterior):
Brick |
|
Items
|
| 1.0 | FLASHINGS Comments: Inspected |
| 1.1 | SKYLIGHTS, CHIMNEYS AND ROOF
PENETRATIONS Comments: Inspected |
| 1.2 | ROOF DRAINAGE SYSTEMS Comments: Inspected |
will be reshape on final prep on the real reports
|
Siding
Style:
Cement stucco Extra Info : stucco |
Driveway:
Concrete |
|
Items
|
| 2.0 | DOORS (Exterior) Comments: Inspected |
| 2.1 | WINDOWS Comments: Inspected |
|
Lock on window in the kitchen
is stuck. window will not open. recommend a license
carpenter for further evaluation
|
| 2.2 | DECKS, BALCONIES, STOOPS, STEPS,
AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE
RAILINGS Comments: Inspected |
|
(1) Note: weather stripping on
the sliding door going outside toward balcony is
coming off.
|
||
(2) Crack on bottom right of
patio sliding door. please consult licensed
carpenter for further evaluation
|
||
(3) Note: Home
front entrance light has gap where debris or insects
can collect and cause potential problems.
|
| 2.3 | VEGETATION, GRADING, DRAINAGE,
DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS
(With respect to their effect on the condition of
the building) Comments: Inspected |
| 2.4 | EAVES, SOFFITS AND FASCIAS Comments: Inspected |
|
Garage
Door Material:
Metal |
Auto-opener
Manufacturer:
LIFT-MASTER |
|
Items
|
| 3.0 | GARAGE CEILINGS Comments: Inspected |
| 3.1 | GARAGE WALLS (INCLUDING FIREWALL
SEPARATION) Comments: Inspected |
| 3.2 | GARAGE FLOOR Comments: Inspected |
| 3.3 | GARAGE DOOR (S) Comments: Inspected |
|
Note: a few
holes on front face of garage door on the outside
where a handle might possibly be.
|
| 3.4 | OCCUPANT DOOR FROM GARAGE TO INSIDE
HOME Comments: Inspected |
|
Power cord for
Garage door opener is not connected and therefore,
it cannot be inspected
|
| 3.5 | GARAGE DOOR OPERATORS (Report
whether or not doors will reverse when met with
resistance) Comments: Not Present |
| Note: Garage Door opener not operated on due to power cord not connected. |
|
Floor
Covering(s):
Carpet Linoleum |
Countertop:
Tile |
|
Items
|
| 4.0 | CEILINGS Comments: Inspected |
| 4.1 | WALLS Comments: Inspected |
|
Note: stain on
wall where the refrigerator is located
|
| 4.2 | FLOORS Comments: Inspected |
| 4.3 | STEPS, STAIRWAYS, BALCONIES AND
RAILINGS Comments: Inspected |
|
Note the rail at
the ground floor is slight loose
|
| 4.4 | COUNTERS AND A REPRESENTATIVE
NUMBER OF CABINETS Comments: Inspected |
| 4.5 | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 4.6 | WINDOWS (REPRESENTATIVE NUMBER) Comments: Inspected |
| Window in kitchen will not open due to broken lock on bottom, recommend licensed carpenter for further evaluation/repair |
|
Foundation:
Poured concrete |
Roof-Type:
Gable Hip |
|
Items
|
| 5.0 | FOUNDATIONS, BASEMENTS AND
CRAWLSPACES (Report signs of abnormal or harmful
water penetration into the building or signs of
abnormal or harmful condensation on building
components.) Comments: Inspected |
| 5.1 | WALLS (Structural) Comments: Inspected |
| 5.2 | FLOORS (Structural) Comments: Inspected |
| 5.3 | CEILINGS (structural) Comments: Inspected |
| Note: did not have good visual to see the ceiling |
| 5.4 | ROOF STRUCTURE AND ATTIC Comments: Not Inspected |
| Note: did not have good visual to do inspection |
|
Water
Filters:
Whole house conditioner (We do not inspect filtration systems) |
Plumbing
Water Distribution (inside home):
PVC |
Water
Heater Power Source:
Gas (quick recovery) |
|
Water
Heater Capacity:
50 Gallon (2-3 people) Unknown |
|
Items
|
| 6.0 | PLUMBING DRAIN, WASTE AND VENT
SYSTEMS Comments: Inspected |
|
(1) Note: crack on 2nd
bathroom upstairs
|
||
(2) Shower/tub
faucet is stuck midway between faucet and shower,
consult a licensed plumber for further evaluation
|
||
(3) downstairs
bathroom at front entrance, leak on sewer line on
sink, wet substance is noticed on floor directly
below pipe. consult licensed plumber for further
evaluation
|
| 6.1 | PLUMBING WATER SUPPLY AND
DISTRIBUTION SYSTEMS AND FIXTURES Comments: Inspected |
| 6.2 | HOT WATER SYSTEMS, CONTROLS,
CHIMNEYS, FLUES AND VENTS Comments: Inspected |
|
(1) Noted Missing earthquake
straps
|
||
(2) Noted Drip
leg on gas line is missing.
|
| 6.3 | MAIN WATER SHUT-OFF DEVICE
(Describe location) Comments: Inspected |
| 6.4 | FUEL STORAGE AND DISTRIBUTION
SYSTEMS (Interior fuel storage, piping, venting,
supports, leaks) Comments: Inspected |
|
Electrical
Service Conductors:
Below ground |
Panel
capacity:
125 AMP |
Panel
Type:
Circuit breakers |
|
Electric
Panel Manufacturer:
SQUARE D |
Branch
wire 15 and 20 AMP:
Copper |
|
Items
|
| 7.0 | SERVICE ENTRANCE CONDUCTORS Comments: Inspected |
|
Note: main panel
out in back missing labeling for all circuit breaker
|
| 7.1 | SERVICE AND GROUNDING EQUIPMENT,
MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION
PANELS Comments: Inspected |
| 7.2 | BRANCH CIRCUIT CONDUCTORS,
OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR
AMPERAGE AND VOLTAGE Comments: Inspected |
| 7.3 | CONNECTED DEVICES AND FIXTURES
(Observed from a representative number operation of
ceiling fans, lighting fixtures, switches and
receptacles located inside the house, garage, and on
the dwelling's exterior walls) Comments: Inspected, Repair or Replace |
|
in the laundry room electrical
plug to the left of the garage door is not working,
recommend license electrician for further evaluation
|
| 7.4 | POLARITY AND GROUNDING OF
RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING
FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT,
EXTERIOR WALLS OF INSPECTED STRUCTURE Comments: Inspected |
| Note with exception of downstairs bathroom, the two bathrooms upstairs both do not have GFCI electrical plugs. |
| 7.5 | OPERATION OF GFCI (GROUND FAULT
CIRCUIT INTERRUPTERS) Comments: Inspected |
| 7.6 | LOCATION OF MAIN AND DISTRIBUTION
PANELS Comments: Inspected |
|
Knock out holes are not
covered. recommend a license electrician for further
evaluation
|
| 7.7 | SMOKE DETECTORS Comments: Inspected |
|
Heat
Type:
Forced Air |
Energy
Source:
Gas |
Number
of Heat Systems (excluding wood):
One |
|
Filter
Type:
Disposable |
Types of
Fireplaces:
Non-vented gas logs |
Operable
Fireplaces:
One |
|
Cooling
Equipment Type:
Air conditioner unit |
|
Items
|
| 8.0 | HEATING EQUIPMENT Comments: Inspected |
| Note: temperature during time of inspection exceeds 80 F, running of heating unit might result in damage to unit. therefore, it was not turned on for inspection. |
| 8.1 | NORMAL OPERATING CONTROLS Comments: Inspected |
| 8.2 | DISTRIBUTION SYSTEMS (including
fans, pumps, ducts and piping, with supports,
insulation, air filters, registers, radiators, fan
coil units and convectors) Comments: Inspected |
| 8.3 | CHIMNEYS, FLUES AND VENTS (for
fireplaces, gas water heaters or heat systems) Comments: Inspected |
| 8.4 | SOLID FUEL HEATING DEVICES
(Fireplaces, Woodstove) Comments: Inspected |
| 8.5 | GAS/LP FIRELOGS AND FIREPLACES Comments: Inspected |
| 8.6 | COOLING AND AIR HANDLER EQUIPMENT Comments: Inspected |
|
| (1) Note: Air filters appears to be dirty. | ||
(2) Note: outside condenser
unit has electrical tape outside of protective mesh.
Unit appears to operate but recommend license
electrical for further evaluation
|
||
(3) Note:
Suction Line show insulation eroding. for optimal
efficiency of unit, insulation should cover entire
Suction line
|
| 8.7 | NORMAL OPERATING CONTROLS Comments: Inspected |
|
temperature for
cooling registered and tested with a laser thermo
reader within the allowable range when tested during
the inspection which is good for the day of the
inspection
|
|
Ventilation:
Soffit Vents |
|
Items
|
| 9.0 | INSULATION IN ATTIC Comments: Not Inspected |
| 9.1 | VENTILATION OF ATTIC AND FOUNDATION
AREAS Comments: Inspected |
| 9.2 | VENTING SYSTEMS (Kitchens, baths
and laundry) Comments: Inspected |
| Vent in the upstairs 2nd bathroom is not working, recommend license electrician for further evaluation |
|
Dishwasher
Brand:
KENMORE |
Built in
Microwave:
FRIGIDAIRE |
|
Items
|
| 10.0 | DISHWASHER Comments: Inspected |
| 10.1 | RANGES/OVENS/COOKTOPS Comments: Inspected |
| Note: Fail safe Hook for range is not present. recommend installation for safety of children. |
| 10.2 | RANGE HOOD Comments: Inspected |
| 10.3 | TRASH COMPACTOR Comments: Inspected |
| 10.4 | MICROWAVE COOKING EQUIPMENT Comments: Inspected |

123 company address
Las Vegas NV 89102
(702) 309-8668
Customer
Mr. first house customer
Address
1287 silver perch
las vegas nv 89123
| 2. Exterior | ||||||||||||||||||||||||
|
||||||||||||||||||||||||
| 6. Plumbing System | ||||||||||||||||||||
|
||||||||||||||||||||
| 7. Electrical System | ||||||||||||||||||||
|
||||||||||||||||||||
| 8. Heating / Central Air Conditioning | ||||||||||
|
||||||||||
| 9. Insulation and Ventilation | |||||||||
|
|||||||||
|
INVOICE |
| Joseph Chan company 123 company address Las Vegas NV 89102 (702) 309-8668 Inspected By: Joseph Chan |
Inspection Date:
9/15/2011 Report ID: 11091501 |
| Customer Info: | Inspection Property: |
| Mr. first house customer 1287 silver perch las vegas nv 89123 Customer's Real Estate Professional: |
1287 silver perch las vegas nv 89123 |
Inspection Fee:
|
||||||||
|
Tax $0.00 |
||||||||
| Total Price $350.00 |
Payment Method: Cash
Payment Status:
Note:
This inspection was performed in accordance with and under the terms of a Pre-Inspection Agreement. The agreement was signed and agreed upon before the preparation of this report and a signed copy of the agreement is available upon request. An unsigned copy of the agreement may be attached to this report for your information or it may also be available on the company web site.